Model:EEP7-12/1600-31.5
Category:Embedded poles
Specifications of Embedded Pole
Main Technical Specification | Unit | Specification | |
1600 | 1250 | ||
Rated voltage | kV | 12 | |
Rated current | A | 1600 | 1250 |
Rated frequency | HZ | 50/60 | |
Short time power frequency withstand voltage(1min) | kV | 79 | |
Lightning impulse withstand voltage | kV | 125 | |
Rated short circuit breaking current | kA | 31.5 | |
Rated peak withstand current | kA | 80 | |
Rated short circuit making current | kA | 80 | |
Rated short time withstand current | kA | 31.5 | |
Rated duration of short circuit | S | 4 | |
Rated breaking current of single capacitor bank | A | 400 | |
Rated breaking current of back to back capacitor bank | A | 400 | |
Rated operating sequence | O-0.3s-CO180s-CO | ||
Breaking operations of rated short circuit breaking current | Times | 30 | |
Rated mechanical endurance | Times | 20000 | |
Closing force due to bellow and atmosphere | N | 140±50 | |
Force required to hold contacts open at full stroke | N | 220±50 | |
Circuit resistance at lower limit of rated contact force | mΩ | ≤25 | |
Contacts limit erosion | mm | 3 | |
Gas pressure inside vacuum interrupter | Pa | ≤1x10?3 | |
Localize discharge | Pc | ≤5 |
Mechanical Data Required for the Matched Vacuum Switchgear
Main Technical Specification | Unit | Specification | |
1600 | 1250 | ||
Clearance between open contacts | mm | 11±1 | |
Average opening speed | m/s | 1.2±0.2 | |
Average closing speed | m/s | 0.6±0.2 | |
Rated of contact force | N | 3100±200 | |
Contact bouncing duration at closing operation | ms | ≤2 | |
Out of simultaneity of contact closing and opening | ms | ≤2 | |
Maximum rebound during opening | mm | ≤2 |