Model:EEP-24/3150-31.5
Category:Embedded poles
Specifications of Embedded Pole
Main Technical Specification | Unit | Specification |
3150 | ||
Rated voltage | kV | 24 |
Rated current | A | 3150 |
Rated frequency | HZ | 50/60 |
Short time power frequency withstand voltage(1min) | kV | 65(79) |
Lightning impulse withstand voltage | kV | 125(145) |
Rated short circuit breaking current | kA | 31.5 |
Rated peak withstand current | kA | 80 |
Rated short circuit making current | kA | 80 |
Rated short time withstand current | kA | 25 |
Rated duration of short circuit | S | 4 |
Rated breaking current of single capacitor bank | A | 400 |
Rated breaking current of back to back capacitor bank | A | 400 |
Rated operating sequence | O-0.3s-CO180s-CO | |
Breaking operations of rated short circuit breaking current | Times | 20 |
Rated mechanical endurance | Times | 10000 |
Closing force due to bellow and atmosphere | N | 100±50 |
Force required to hold contacts open at full stroke | N | 200±50 |
Circuit resistance at lower limit of rated contact force | mΩ | ≤25 |
Contacts limit erosion | mm | 3 |
Gas pressure inside vacuum interrupter | Pa | ≤1x10?3 |
Localize discharge | Pc | ≤5 |
Mechanical Data Required for the Matched Vacuum Switchgear
Main Technical Specification | Unit | Specification |
3150 | ||
Clearance between open contacts | mm | 13±1 |
Average opening speed | m/s | 1.3±0.2 |
Average closing speed | m/s | 0.6±0.2 |
Rated of contact force | N | 3150±200 |
Contact bouncing duration at closing operation | ms | ≤2 |
Out of simultaneity of contact closing and opening | ms | ≤2 |
Maximum rebound during opening | mm | ≤2 |