Model:VITD12/2000-31.5
Category:VI for indoor circuit breakers
Main Technical Specification | ||
VOLTAGE RATINGS | ||
Rated voltage(Ur) | kV | 12 |
Rated short-time(1min)power-frequency withstand voltage(Ud) | kV | 48 |
Rated lightning impulse withstand voltage(Peak)(Up) | kV | 85 |
Rated frequency(fr) | Hz | 50 |
CURRENT RATINGS | ||
Rated current(Ir) | A | 1250/1600/2000 |
Circuit resistance at lowest rated contact force | μΩ | ≤15 |
Rated short-circuit breaking current(lsc) | kA | 31.5/40 |
Breaking operations of rated short circuit breaking current | Times | 30 |
Rated short-time withstand current(lk) | kA | 31.5/40 |
Rated duration of short-circuit(tk) | s | 4 |
Rated peak withstand current(lp) | kA | 80/100 |
Rated short-circuit making current(lMc) | kA | 80/100 |
Rated cable-charging breaking current(lc) | A | 25 |
Rated breaking current of single capacitor bank(lsb) | A | 400 |
Rated breaking current of back-to-back capacitor bank(lbb) | A | 400 |
MECHANICAL DATA | ||
Weight of movable parts | kg | ≤1.6 |
Closing force due to bellow and atmosphere | N | 150±50 |
Force required to hold contacts open at full stroke | N | 190±60 |
MECHANICAL REQUIREMENTS | ||
Clearance between open contacts | mm | 11±1 |
Average opening speed (contact close position~75%contact gap) | m/s | 1.0±0.25 |
Average closing speed (30%contact gap-contact close position) | m/s | 0.6±0.15 |
Rated added external contact final force | N | 4250±250 |
3200±200 | ||
Added external contact force at contact touch point | 3000±200 | |
2300±200 | ||
Contact bouncing duration at closing operation | ms | ≤2 |
Closing and opening non-simultaneity of three-phase contacts | ms | ≤1 |
Maximum rebound during opening | mm | ≤3 |
LIFE | ||
Storage life | years | 20 |
Rated mechanical endurance | Times | 10000 |
Contacts limit erosion | mm | 3 |