Model:VITJ12/630-6.3
Category:VI for contactors
Main Technical Parameter | ||
Rated voltage | 12kV | |
Rated current | 630A | |
Rated frequency | 50Hz | |
Rated short-time Power frequency withstand voltage | 42kV | |
Rated lightning impulse withstand voltage | 75kV | |
Rated making current | 6300A | |
Rated switching current | 5000A | |
Limit switching current | 6000A | |
Withstand overload current | 6300A | |
Electrical endurance AC-3 | 250000 times | |
Electrical endurance AC-4 | 10000 times | |
Mechanical endurance | 300000 times | |
Closing force due to bellow and atmosphere | 70±30N | |
Force required to hold contacts open at full storke | 100±40N | |
Circuit resistance at lowest rated contact force | ≤60μ? | |
Storage life | 20 years | |
Contacts limit erosion | 3mm | |
Weight of movable parts | ≤0.7kg | |
MECHANICAL DATA REQUIRED FOR THE MATCHED VACUUM SWITCHGEAR | ||
Clearance between open contacts | 6±1 mm | |
Contact connection stroke | 3±0.5mm | |
Average opening speed | 0.4-0.5m/s | |
Average closing speed | 0.15-0.25m/s | |
Rated added extemal contact final force | 220±10N | |
Contact bouncing duration at closing operation | ≤2 ms | |
Closing and opening non-simultaneity of three-phase contacts | ≤2 ms |